Impact Tech Solutions · HSE Calculators
VENTILATION ACH

Ventilation Air Change Rate (ACH) Calculator

ACH = Air Changes per Hour. Calculates room air change rate from airflow and volume, and the time required to clear airborne contaminants to a target efficiency, per CDC environmental infection control guidance.
ACH & Airflow
Contaminant Clearance Time
Room Dimensions
Airflow
0 ft³
Room Volume
0
Air Changes per Hour
0
MINUTES TO TARGET CLEARANCE

Formula Reference

Room Volume = Length × Width × Height
ACH = (Airflow Rate × 60) ÷ Room Volume
Required Airflow = (Target ACH × Room Volume) ÷ 60
Clearance Time (minutes) = − ln(1 − Efficiency÷100) ÷ ACH × 60 × Mixing Factor (k)

CDC Reference: Time for Airborne Contaminant Removal (k = 1)

4 ACH69 min (99%) / 104 min (99.9%)
6 ACH46 min (99%) / 69 min (99.9%)
10 ACH28 min (99%) / 41 min (99.9%)
12 ACH23 min (99%) / 35 min (99.9%)
15 ACH18 min (99%) / 28 min (99.9%)
20 ACH14 min (99%) / 21 min (99.9%)

Commonly Cited ACH Recommendations

Operating rooms≥ 15–20 ACH
Airborne infection isolation room (new construction)≥ 12 ACH
Airborne infection isolation room (existing)≥ 6 ACH
Patient/treatment rooms, ER waiting areas6–12 ACH