Ventilation Air Change Rate (ACH) Calculator
ACH = Air Changes per Hour. Calculates room air change rate from airflow and volume, and the time required to clear airborne contaminants to a target efficiency, per CDC environmental infection control guidance.
ACH & Airflow
Contaminant Clearance Time
Formula Reference
Room Volume = Length × Width × Height
ACH = (Airflow Rate × 60) ÷ Room Volume
Required Airflow = (Target ACH × Room Volume) ÷ 60
Clearance Time (minutes) = − ln(1 − Efficiency÷100) ÷ ACH × 60 × Mixing Factor (k)
CDC Reference: Time for Airborne Contaminant Removal (k = 1)
| 4 ACH | 69 min (99%) / 104 min (99.9%) |
| 6 ACH | 46 min (99%) / 69 min (99.9%) |
| 10 ACH | 28 min (99%) / 41 min (99.9%) |
| 12 ACH | 23 min (99%) / 35 min (99.9%) |
| 15 ACH | 18 min (99%) / 28 min (99.9%) |
| 20 ACH | 14 min (99%) / 21 min (99.9%) |
Commonly Cited ACH Recommendations
| Operating rooms | ≥ 15–20 ACH |
| Airborne infection isolation room (new construction) | ≥ 12 ACH |
| Airborne infection isolation room (existing) | ≥ 6 ACH |
| Patient/treatment rooms, ER waiting areas | 6–12 ACH |