Flammable Liquid Storage Quantity Calculator
Checks planned flammable liquid storage quantities against OSHA 29 CFR 1910.106(d)/(e) limits for storage cabinets and incidental (outside-cabinet) storage per fire area.
Scope note: This tool covers OSHA 1910.106(d)(3) storage cabinet limits and 1910.106(e)(2)(ii) incidental storage limits only — the two most commonly needed checks. It does not cover inside storage room construction/ventilation requirements, outdoor pile storage, tank storage, or the full NFPA 30 Maximum Allowable Quantity (MAQ) per control area tables, which depend on occupancy type, construction, and sprinkler protection. Verify classification against each liquid's SDS (Section 9) and confirm final storage arrangement with your local Authority Having Jurisdiction (AHJ).
Storage Cabinet(s)
Incidental Storage (No Cabinet)
OSHA 1910.106(d)(3) — Storage Cabinet Limits
| Category 1, 2, or 3 combined | Max 60 gallons per cabinet |
| All categories combined (incl. Category 4) | Max 120 gallons per cabinet |
| Cabinets per fire area | Max 3 without sprinkler protection/AHJ approval (beyond 3, separate by 100 ft or use an inside storage room) |
OSHA 1910.106(e)(2)(ii) — Incidental Storage (No Cabinet)
| Category 1 in containers | Max 25 gallons per fire area |
| Categories 2, 3, 4 in containers | Max 120 gallons per fire area |
| Single portable tank | Max 660 gallons |
Per OSHA's own clarifying interpretation letter, the 60-gallon and 120-gallon cabinet limits are
not additive — a cabinet holds at most 120 gallons total, of which no more than 60 gallons may be Category 1, 2, or 3 liquid.