Calculates the minimum number of portable fire extinguishers needed for a floor area, per NFPA 10 (Standard for Portable Fire Extinguishers) hazard classification, floor-area coverage, and maximum travel distance.
—
Minimum Extinguisher Rating
0 ft
Max Travel Distance
0
Minimum Extinguishers Required
Formula Reference
Extinguishers by Floor Area = ⌈ Floor Area ÷ Max Area per Unit ⌉ (Class A only \u2014 NFPA 10 Table 6.2.1.1)
Grid Spacing (travel-distance based) = Max Travel Distance ÷ √2
Extinguishers by Travel Distance = ⌈ Floor Area ÷ Grid Spacing² ⌉ Required = the larger of the two figures (both must be satisfied)
NFPA 10 Table 6.2.1.1 — Class A
Light Hazard
2-A min · 3,000 ft²/unit · 75 ft travel
Ordinary Hazard
2-A min · 1,500 ft²/unit · 75 ft travel
Extra Hazard
4-A min · 1,000 ft²/unit · 75 ft travel
Class B & K Travel Distance
Class B
2-A:10-B:C (ordinary) / 4-A:40-B:C (extra) min · 30–50 ft travel depending on rating (NFPA 10 Table 6.3.1.1)
Class K
30 ft travel from cooking appliances (must supplement, not replace, Class A/B/C coverage — NFPA 10 §5.6.2 / NFPA 96)
Note: the 75 ft Class A travel distance applies at all hazard levels \u2014 what changes with hazard level is the minimum rating and maximum floor area per unit, not the travel distance itself.