Impact Tech Solutions · HSE Calculators
EVACUATION TIME

Evacuation Time Calculator

Estimates total building/area evacuation time from occupant load and exit width, using the SFPE (Society of Fire Protection Engineers) hydraulic flow-calculation approach: pre-movement time + travel time + exit queuing/discharge time.
Occupancy & Exits
Timing Factors
0.0
Exit Queuing Time (s)
0.0
Travel Time (s)
0.0
Total Evacuation Time (s)

Formula Reference

Effective Width per Exit = Clear Width − Boundary Layer Loss
Exit Flow Capacity = (Effective Width × Number of Exits) × Specific Flow Rate
Exit Queuing Time = Occupant Load ÷ Flow Capacity
Travel Time = Travel Distance ÷ Walking Speed
Total Evacuation Time = Pre-Movement Time + Travel Time + Exit Queuing Time
Doors / Corridors (IBC/SFPE)~78.7 persons/min per metre width (24/ft/min)
Stairways (IBC/SFPE)~59.1 persons/min per metre width (18/ft/min)
Typical boundary layer loss150–200 mm per exit, per SFPE Handbook

Benchmark Guidance

There is no single universal pass/fail time — acceptable evacuation time depends on occupancy type, building complexity, and applicable code. As a general reference point, BS 9999 (British Standard for fire safety in building design) suggests around 2.5 minutes for low-complexity buildings, up to 5 minutes for more complex ones; many workplace fire risk assessments target under 3 minutes for straightforward office/industrial layouts. Always confirm the applicable target against your local fire code and a qualified fire safety engineer.